Burner Management and Ignition Systems


Orifice Fittings and Meter Runs | Burner Management and Ignition Systems | Digital Test Gauge | Remanufactured Equipment


CAN-LITE MODEL 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor
- Download PDF Version
Safe and reliable flame failure protection and ignition combined with a proven pilot head; completely self-powered. The Can-Lite 800 provides safe, economical and reliable burner control on most industrial gas fired heater applications. Ideal for line heaters, dehy. and de-eth. reboilers, treaters
Features
• Heavy duty low temperature piezo electric igniter provides reliable self-powered ignition
• Failsafe thermocouple powered gas valve ensures the pilot flame is proven before the main fuel valve will open
• Integral Venturi System aspirates combustion air through a built-in flame arrester
• Built-in automatic lockout eliminates the need for costly auxiliary controls
• Unique 316 SS pilot assembly easily installs and retracts thru a standard 1" NPT collar
• The low fuel consumption design enables feasible natural gas or propane operation
• Stainless steel and aluminum construction
• Hi-temp Mica Ignition lead channeled through the mixing tube eliminates lead deterioration
 

Specifications
Operating Temperature -40C to +85C
Materials and Parts Anodized Aluminum, 316 SS
Valve Seals Buna N Standard, Viton Optional
Gauge Ports 1/8" NPT
Supply / Output Ports 1/4" NPT
Max. W.P. 30 PSI
Mix. W.P. 5 PSI
Mounting 1" Male NPT
Supply Pressure Filtered 20 PSI Natural Gas or Propane
Pilot Fuel Consumption 7 SCFH, 7,000 BTU/Hr.
Ignition 15KV Low Temp. Piezo
Environment Rating Class 1, Div. 2 Hazardous Location
Power Self Powered - 30mV Thermopile
Insertion Length Multiples of 1 ft. or Custom Built
Main Gas Direct Feed 750,000 BTU/Hr

Ordering Information